Level sensor
Description

ENW-E12 230VAC - Art. no. 110308-05
ENW-E12 24VAC -  Art. no. 110308-10

The level sensor monitors filling levels or leakage of all conductive, noncombustible media. The trigger can be adjusted by means of a proportional potentiometer. As monitor, the device works with an electrode (EO) and the ground connection (EM), e.g. for minimum and maximum levels, to protect submersible pumps from overflowing or running dry. If the surface of the fluid is subject to disturbance, we recommend another electrode (EU). As two-level controller, the device controls pumps or valves for automatically filling and emptying containers by means of the EO and EU electrodes and the EM ground connection. A container wall, being conductive to the medium, can also be used as ground connection. Variants: 230 V AC or 24 V AC

Features:

  • Input up to 3 electrodes
  • adjustable sensitivity 5 to 50kOhm
  • Operating voltage UN 230 V AC, 24 V AC
  • Output contact 2 changeover contacts (2 DPST)
  • Switching voltage max. 250 V AC
  • Continuous current max. 6 A
  • Dimensions W x H x D 22,5 x 75 x 100 mm
  • Operation temperature range 0 °C ... +55 °C
  • Storage temperature range -20 °C ... +70 °C